FVR-C11S-EN
Contents
Safety Instructions
................................... 1
1 Before Using This Product
........... 1-1
1-1 Receiving Inspections ................... 1-1
1-2 Appearance .................................. 1-2
1-3 Handling the Product .................... 1-3
1-4 Carrying ........................................ 1-4
1-5 Storage and transportation ........... 1-4
2 Installation and Connection
........... 2-1
2-1 Operating Environment ................. 2-1
2-2 Installation Method ........................ 2-2
2-3 Connection .................................... 2-3
2-3-1 Basic connection .................... 2-3
2-3-2 Connecting the main circuit
and ground terminals ............. 2-4
2-3-3 Connecting the
control terminals ..................... 2-6
2-3-4 Connection examples ........... 2-12
2-4 Others ......................................... 2-21
2-4-1 Harmonic component ........... 2-21
2-4-2 Noise .................................... 2-21
2-4-3 Leakage current ................... 2-21
3 Operation
............................................ 3-1
3-1 Inspection and Preparation
before Operation ........................... 3-1
3-2 Operation Method ......................... 3-1
3-3 Trial Run ....................................... 3-2
4 Keypad Panel
.................................... 4-1
4-1 Names and Functions ................... 4-1
4-2 Operating Keypad Panel ............... 4-1
5 Selecting Function
........................... 5-1
5-1 Function Selection List .................. 5-1
5-2 Details of Each Function ............... 5-7
6 Protective Function
......................... 6-1
6-1 List of protective functions ............ 6-1
6-2 Alarm Reset .................................. 6-3
7 Troubleshooting
............................... 7-1
7-1 In case of tripping ......................... 7-1
7-2 Other trouble ................................. 7-7
8 Maintenance and Inspection
.......... 8-1
8-1 Daily Inspection ............................. 8-1
8-2 Periodic Inspection ........................ 8-1
8-3 Electrical measurements
in the Main Circuit ......................... 8-5
8-4 Insulation Test ............................... 8-6
8-5 Parts Replacement ....................... 8-7
8-6 Inquiries about the Product and
Guarantee of the product .............. 8-7
9 Specifications
.................................... 9-1
9-1 Standard Specifications ................ 9-1
9-2 Common Specifications ................ 9-2
9-3 Dimensions ................................... 9-8
9-4 Selection of Peripheral Device .... 9-11
10 Options
............................................ 10-1
10-1 Built-in Options ............................ 10-1
10-2 External Options ......................... 10-1
11 Applicable reactors
....................... 11-1
12 Compliance with standards
........ 12-1
12-1 UL/cUL standards [Applicable to
products with UL/cUL mark]......... 12-1
12-1-1 General ................................. 12-1
12-1-2 Precautions ........................... 12-1
12-2 Compliance with EMC directive
in EU [Applicable to products
with CE mark] .............................. 12-2
12-2-1 General ................................ 12-2
12-3 Compliance with low voltage directive
in EU [Applicable to products
with TÜV or CE mark] .................. 12-2
12-3-1 General ................................. 12-2
12-3-2 Precautions ........................... 12-2
13 Electromagnetic
Compatibility (EMC)
....................... 13-1
13-1 General ....................................... 13-1
13-2 RFI Filters ................................... 13-1
13-3 Recommended Installation
Instructions .................................. 13-3
FVR-C11S-EN
Contents
Safety Instructions
................................... 1
1 Before Using This Product
........... 1-1
1-1 Receiving Inspections ................... 1-1
1-2 Appearance .................................. 1-2
1-3 Handling the Product .................... 1-3
1-4 Carrying ........................................ 1-4
1-5 Storage and transportation ........... 1-4
2 Installation and Connection
........... 2-1
2-1 Operating Environment ................. 2-1
2-2 Installation Method ........................ 2-2
2-3 Connection .................................... 2-3
2-3-1 Basic connection .................... 2-3
2-3-2 Connecting the main circuit
and ground terminals ............. 2-4
2-3-3 Connecting the
control terminals ..................... 2-6
2-3-4 Connection examples ........... 2-12
2-4 Others ......................................... 2-21
2-4-1 Harmonic component ........... 2-21
2-4-2 Noise .................................... 2-21
2-4-3 Leakage current ................... 2-21
3 Operation
............................................ 3-1
3-1 Inspection and Preparation
before Operation ........................... 3-1
3-2 Operation Method ......................... 3-1
3-3 Trial Run ....................................... 3-2
4 Keypad Panel
.................................... 4-1
4-1 Names and Functions ................... 4-1
4-2 Operating Keypad Panel ............... 4-1
5 Selecting Function
........................... 5-1
5-1 Function Selection List .................. 5-1
5-2 Details of Each Function ............... 5-7
6 Protective Function
......................... 6-1
6-1 List of protective functions ............ 6-1
6-2 Alarm Reset .................................. 6-3
7 Troubleshooting
............................... 7-1
7-1 In case of tripping ......................... 7-1
7-2 Other trouble ................................. 7-7
8 Maintenance and Inspection
.......... 8-1
8-1 Daily Inspection ............................. 8-1
8-2 Periodic Inspection ........................ 8-1
8-3 Electrical measurements
in the Main Circuit ......................... 8-5
8-4 Insulation Test ............................... 8-6
8-5 Parts Replacement ....................... 8-7
8-6 Inquiries about the Product and
Guarantee of the product .............. 8-7
9 Specifications
.................................... 9-1
9-1 Standard Specifications ................ 9-1
9-2 Common Specifications ................ 9-2
9-3 Dimensions ................................... 9-8
9-4 Selection of Peripheral Device .... 9-11
10 Options
............................................ 10-1
10-1 Built-in Options ............................ 10-1
10-2 External Options ......................... 10-1
11 Applicable reactors
....................... 11-1
12 Compliance with standards
........ 12-1
12-1 UL/cUL standards [Applicable to
products with UL/cUL mark]......... 12-1
12-1-1 General ................................. 12-1
12-1-2 Precautions ........................... 12-1
12-2 Compliance with EMC directive
in EU [Applicable to products
with CE mark] .............................. 12-2
12-2-1 General ................................ 12-2
12-3 Compliance with low voltage directive
in EU [Applicable to products
with TÜV or CE mark] .................. 12-2
12-3-1 General ................................. 12-2
12-3-2 Precautions ........................... 12-2
13 Electromagnetic
Compatibility (EMC)
....................... 13-1
13-1 General ....................................... 13-1
13-2 RFI Filters ................................... 13-1
13-3 Recommended Installation
Instructions .................................. 13-3
2 Safety Instructions
FVR-C11S-EN
Compliance with UL/cUL standards [Applicable to products with UL/cUL mark]
1. [WARNING] Take care of electric shock. Be sure to turn the
inverter off before starting work.
2. [CAUTION] When the charge lamp is lit, the inverter is still charged
at a dangerous voltage.
3. [WARNING] There are two or more live parts inside the inverter.
4. The inverter is approved as a part used inside a panel. Install it inside
a panel.
5. Perform wiring to the input, output and control terminals of the inverter,
referring to the table below. Use UL certified round crimp
terminal to the input and output terminals with insulation cover or
covered with reduced tube to obtain the insulation distance. Use a
crimping tool recommended by the terminal manufacturer when
fabricating crimp terminals.
6. Install a fuse in the power supply to the inverter, referring to the table
below.
Voltage Inverter type
Tightening torque
[Nm]
Applicable wire diameter
[AWG] (mm
Fuse
[A]
2)
Recommended fuse
L1/L, L2/N
U, V, W
Control
section
L1/L, L2/N
U, V, W
Control
section
Gould
Company
Bussmann
Company
Singlephase
200V
input
FVR0. 1C11S-7EN
1.2
0.4
14 (2.1)
20 (0.5)
6 A4J6 JKS6
FVR0. 2C11S-7EN 6 A4J6 JKS6
FVR0. 4C11S-7EN 10 A4J10 JKS10
FVR0. 75C11S-7EN 15 A4J15 JKS15
FVR1. 5C11S-7EN 12 (3.3) 30 A4J30 JKS30
FVR2. 2C11S-7EN 1.8 10 (5.3) 40 A4J40 JKS40
1) Use copper wires of allowable maximum temperature 60 or75 °C.
2) Use UL certified "quick breaking fuse".
7. Connect the power supply satisfying the characteristics shown in
the table below as an input power supply of the inverter. (Short
circuit rating)
Inverter type Input max. voltage Input current
FVR0. 1-2. 2C11S-7EN AC240V 5,000 A or less
CAUTION
Safety Instructions 3
FVR-C11S-EN
Compliance with low voltage directive in
EU [Applicable to products with TÜV
mark]
CAUTION
1. Safe separation for control interface of this
inverter is provided when this inverter is installed
in overvoltage category II. PELV
(Protective Extra Low Voltage) circuit or
SELV (Safety Extra Low Voltage) circuit
from external controller is connected to the
interface directly.
2. Basic insulation for control interface of this
inverter is provided when this inverter is installed
in overvoltage category III. An insulation
transformer has to be installed
between power supply mains and this inverter
when SELV circuit from external
controller is connected to this inverter directly.
Otherwise supplementary insulation
between control interface of this inverter
and environment must be provided.
3. The ground terminal G should always be
connected to the ground. Don’t use only
RCD as the sole method of electric shock
protection. Dimensions of external PE conductor
should be same as dimensions of
input phase conductor and capable for
possible fault.
4. Use MCCB or MC that conforms to EN or
IEC standard.
5. Where RCD (Residual-current-operated
protective device) is used for protection in
case of direct or indirect contact, only
RCD
of type B
is allowed on the supply side of
this EE (Electric equipment). Otherwise another
protective measure shall be applied
such as separation of the EE from the environment
by double or reinforced insulation
or isolation of EE and supply system
by the transformer.
6. The inverter has to be installed in environment
of pollution degree 2. If the environment
is pollution degree 3 or 4, the
inverter has to be installed in a cabinet of
IP54 or higher.
7. Use a prescribed wire according to the
EN60204 Appendix C.
8. Install the inverter, AC or DC reactor, output
filter in an enclosure that meets the
following requirement, to prevent a human
body from touching directly to these
equipment.
1) When a person can touch easily on each
connecting terminal or live parts, install
the inverter, AC or DC reactor, output filter
in an enclosure with minimum degree
of protection of IP4X.
2) When a person can not touch easily on
each connecting terminal or live parts,
install the inverter, AC or DC reactor,
output filter in an enclosure with a minimum
degree of protection of IP2X.
9. It is necessary to install the inverter in appropriate
method using an appropriate
RFI filter to conform to the EMC directive.
It is customer’s responsibility to check
whether the equipment, the inverter is installed
in, conforms to EMC directive.
4 Safety Instructions
FVR-C11S-EN
Compliance with low voltage directive in EU [Continued]
Use of wires specified in Appendix C of EN 60204 is recommended.
Power
supply
voltage
Nominal
applied
motor
[kW]
Inverter type
Molded case circuit
breaker (MCCB) or
earth leakage
circuit breaker
(ELCB)
1)
Rated current [A]
Recommended wire size [mm
2
]
Input circuit
2)
single phase
200V [L1/L, L2/N]
Output
circuit
2)
[U, V, W]
DCR
2)
circuit
[P1]
[P(+)]
Control
wiring
With
DCR
Without
reactor
3)
With
DCR
Without
reactor
3)
Single
phase
200V
0.1 FVR0. 1C11S-7EN
6
6
2.5
4)
2.5
4)
2.5
4) 2.5
4)
0.5
0.2 FVR0. 2C11S-7EN
0.4 FVR0. 4C11S-7EN 10
0.75 FVR0. 75C11S-7EN 10 16
1.5 FVR1. 5C11S-7EN 16 20
4.0
4)
2.2 FVR2. 2C11S-7EN 20 32
4.0 5) 6.0 5) 2.5 5) 4.0
5)
1) The applicable frame and series of the molded case circuit breaker (MCCB) and
earth leakage circuit breaker (ELCB) vary according to the capacity of the
transformer of the equipment. For details of selection, refer to the concerning
technical documents.
2) The recommended wire size for the main circuit is the case for the low voltage
directive at ambient temperature 40 °C.
3) The power supply impedance without a reactor is considered to be the
equivalent of 0.1% of the inverter capacity, with 10% current imbalance
accompanied by the voltage imbalance.
4) Crimp terminals up to 7.4 mm in width (including tolerance) can be used.
5) Crimp terminals up to 9.5 mm in width (including tolerance) can be used.
6) Use the grounding cable of a size equal to or larger than that of the input power
supply cable.
CAUTION